Royce Thompson V400 /1 25 - 50000lux adjustable photocells with integral ‘press to test’ capability are ideal for control of lighting circuits where lux level adjustment is required along with remote detection. A special ‘reserve acting’ variant is available to meet the special requirements of tunnel and underpass lighting.
V400 /1 Photocell Specification:
Sensor type: Cadmium sulphide. Operating voltage: 230 Vac +/- 10%, 50/60 Hz. Maximum lamp load (HID): 3 x 400W 96µF. 8A (res). Switching differential: 1:1.5 positive. Switching range: 25 – 2000 Lux. Power consumption: 0.6W. Operating temperature range: -20 / +80°C Warranty: 2 years. Ingress protection: IP65 (detector) IP54 (housing)
7TCA230150R0091
TP871104110PT